+380 (44) 465 7263
Air heating units
TORNADO VX1
TORNADO VX3
 - Technical parameters
 - Construction
 - Control elements
 - Installation
TORNADO VX5
TORNADO VX7
TORNADO VXD

Installation TORNADO VX3

Mounting
Wall mounting Ceiling mounting
The wall interval                         min. 0,25 m The ceiling interval                         min. 0,25 m
Mounting altitude                               3 - 8 m Mounting altitude                                 4 - 12 m
Air stream range                          max. 25 m 

* directing louvers are adjusted horizontally
** directing louvers are adjusted vertically 
*** directing louvers are adjusted symmetrically at the angle of 45°

Heat medium pipe



When connecting a heat medium pay your attention that manifolds of the heaters must be fixed. For this use two keys: one – for fixing heat exchanger manifolds, the second – for connecting it to the system.
Installation of a few units:







When mounting a few TORNADO unit heaters it is recommended to stick to the following intervals between units: installation in one line – 5-9 m, installation opposite to each other – 27-35 m, installation one by one – 12-15 m. These intervals are just recommendations. The installer should also take into account dimensions and shape of a building, its encumbering, and recommendations of specialists on a project.
Main Page » Products » Air heating units » TORNADO VX3 » Installation

 
 
 
 
       
© TORNADO 2009-2014. All rights reserved.
 

Contacts

+380 (44) 465 7263